Bently Nevada 3500 System
Brand | Bently Nevada |
Item No | 3500 System |
Part Number | 3500 System |
Series | 3500 |
Origin | United States (US) |
Dimension | 119*189*135(mm) |
Weight | 1.2kg |
Customs Tariff Number | 85389091 |
Condition | Brand new and original |
Quality Guarantee | 1 Year |
Payment | T/T |
Delivery Time | 2-3 day |
Shipping Port | China |
Product Information
Bently Nevada 3500 System
The 3500 System provides continuous, online monitoring suitable for machinery protection applications, and is designed to meet the requirements of the American Petroleum Institute’s API 670 standard for such systems. The system’s modular rack-based design includes the following components:
*3500/05 Instrument Rack (required)
*One or two 3500/15 Power Supplies (required)
*3500/22M Transient Data Interface (TDI) Module (required)
*One or more 3500/XX Monitor Modules (required)
*One or more 3500/32M (4-channel) or 3500/33 (16-channel) Relay Modules (optional)
*One or two 3500/25 Keyphasor* Modules (optional)
*One or more 3500/92 Communication Gateway Modules (optional)
*Input/Output (I/O) Modules (required)
*3500/94M VGA Display (optional)
*Internal or external intrinsic safety barriers, or galvanic isolators for hazardous area installations (optional)
*3500 System Configuration Software (required)
1.Power Supplies: This particular rack has an AC-powered supply in the primary (lower) position, and a DC-powered backup supply in the upper position.
2.Keylock security prevents tampering with the configuration of the monitors in the rack.
3.Transient Data Interface (TDI): Provides an interface to configuration software and to System 1 Condition Monitoring & Diagnostic software. It also coordinates communication between all modules in the rack.
4.Keyphasor Module: Accepts single and multi-event per-rotation signals from proximity probes and magnetic pickups installed on rotating equipment.
5.3500/72M (Recip Rod Position) and 3500/77M (Recip Cylinder Pressure) monitors are used for condition monitoring of reciprocating compressors.
6.60/61 Temperature Monitors.
7.3500/42M Proximitor/Seismic vibration monitors.
8.Buffered transducer signals are provided for use with portable test instruments.
9.Unused slots are protected with “Future Expansion” covers, and are available for use with additional modules.
10.3500/33 16-Channel Relay Module.
11.3500/92 Modbus® Communication Gateway.
12.Standard rack for 19” EIA rail mounting.